Underground CCA Conductor PVC Armoured XLPE Insulated Power Cable
Underground CCA Conductor PVC Armoured XLPE Insulated Power Cable image
Power Cable Underground Aluminum/Copper CCA Conductor XLPE Insulation PVC Jacket Armoured Cable
APPLICATIONS:
The single core cables are designed for distribution of electrical power with nominal voltage Uo/U ranging from 3.8/6.6KV to 19/33KV and frequency 50Hz. They are suitable for installation mostly in power supply stations, indoors and in cable ducts, outdoors, underground and in water as well as for installation on cable trays for industries, switchboards and power stations.
STANDARD:
BS 6622
BS 7835 (LSZH Version)
Noted:Single Core Cables to BS 6622/BS 7835/IEC 60502/VDE 0276
Cable Construction
medium voltage cables are manufactured using the monosil process. We provide the highly specialized plant, state-of-the-art research facilities and meticulous quality control procedures that are required for the manufacturing of PVC insulated cables for use up to 6KV and XLPE/EPR insulated cables for use at voltages up to 35 KV. The materials are all kept in cleanliness-controlled conditions throughout the production process in order to ensure the absolute homogeneity of the finished insulation materials.
Conductors
Either aluminium or copper conductors are used. Conductors up to 630mm² will be circular, compacted & stranded and shall comply with IEC 60228 class 2. 630mm² conductor will be circular stranded type on which a layer of semi-conducting tape will be applied.
Conductor Screen
This will be an extruded layer of semi-conducting crosslinkable compound applied under simultaneous triple extrusion process over the conductor along with the insulation and the insulation screen. The triple extrusion is a single high precision operation that eliminates the possibility of any contamination between the layers which could create irregularities in the electrical field. By careful material selection and special attention to process parameters, we produce the insulation screen layers with the required degree of stripping force as stipulated by the applicable national or international standard.
Insulation
This will be an extruded layer of XLPE applied over conductor screen under triple extrusion process along with conductor screen and insulation screen.
Insulation Screen
This will be a layer of semi-conducting crosslinkable compound which will be applied by triple extrusion process over the insulation.
Metallic Screen
It will consist of a layer of copper tape applied helically with overlap over insulation screen. Other combinations of metallic screens as per customer ’s requirement can also be provided on request.
Laying-Up
In case of three core cables, the three cores are laid up with non-hygroscopic fillers like polypropylene(PP) fillers at interstices and a binder tape is applied with an overlap. These binder tapes can be of PVC or foamed Polyethylene.
Inner Sheath (Bedding) for Armoured Cables
Extruded layer of PVC or PE is applied over the laid up cores for armoured cables. PVC is normally of grade ST2 and PE of grade ST7 as per IEC 60502 Part 2.
Armouring
In case of armoured cables, the armour is applied helically over inner sheath. For single core cables, it is of aluminium wires and for multicore cables, the armour can be of one among the following options:
a) Galvanized steel wire.
b) Galvanized steel tape.
Over Sheath
An extruded layer is applied over the armour in case of armoured cables and over laid up cores in case of unarmoured cables. Outer sheath material can be either PVC, PE, HDPE or MDPE. our
medium voltage cables are normally supplied with red PVC over sheaths complying with BS 6622 or IEC 60502. Other colors may be provided to suit a range of installation considerations such as the effect of UV radiations and differing soil compositions. Anti-termite formulations can also be supplied in addition to graphite-coated over sheaths where on-site testing of the sheath is required.
Fire Performance on Cable Sheaths
Cables can also be supplied with special flame retardant PVC over sheaths to comply with the IEC 60332 standard. We can also supply cables with Low Smoke Halogen Free (LSZH) sheaths according to BS 7211 and BS 6724 standards or other equivalent international standards.
Cable Parameters:
6/10KV Medium Voltage Single Core Power Cable (Amoured)
Nom. Cross-Section Area |
Aluminium Wire Armoured Cables | |||||
Nom. Bedding Thickness | Armour Wire Size | Nom. Sheath Thickness | Approx. Overall Diameter | kg/km | ||
mm² | mm | mm | mm | mm | ||
16 | 1.2 | 1.6 | 1.8 | 24 | 770 | 670 |
25 | 1.2 | 1.6 | 1.8 | 25 | 910 | 750 |
35 | 1.2 | 1.6 | 1.8 | 26 | 1040 | 820 |
50 | 1.2 | 1.6 | 1.8 | 28 | 1190 | 900 |
70 | 1.2 | 1.6 | 1.9 | 29 | 1470 | 1040 |
95 | 1.2 | 1.6 | 2 | 31 | 1780 | 1190 |
120 | 1.2 | 2 | 2 | 34 | 2150 | 1410 |
150 | 1.2 | 2 | 2.1 | 35 | 2480 | 1560 |
185 | 1.2 | 2 | 2.1 | 37 | 2890 | 1730 |
240 | 1.2 | 2 | 2.2 | 40 | 3570 | 2050 |
300 | 1.2 | 2 | 2.3 | 42 | 4230 | 2330 |
400 | 1.3 | 2.5 | 2.4 | 47 | 5320 | 2890 |
500 | 1.4 | 2.5 | 2.5 | 51 | 6510 | 3530 |
630 | 1.5 | 2.5 | 2.6 | 56 | 7960 | 4050 |
Why Choose Zhenglan Cable:
- OEM/ODM services provided;
- Products comply with GB, IEC, BS, ASTM, DIN, VDE and JIS standards; Customer standard requirments Accepted;
- Certified to ISO 9001:2015, ISO 14001:2015 and OHSAS 18001:2007;
- Registered capital of $30 million and factory covers an area of 60,000㎡;
- Advanced test equipment and procedures, 100% inspection before factory;
- Enough stocks and the higest efficient shipping time guarranteed;
- Professional pre-sales and after-sales services provided.
We are China Underground CCA Conductor PVC Armoured XLPE Insulated Power Cable manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Tags: Medium Voltage Power Cables, PVC xlpe medium voltage cables, Underground armoured electrical cable