SWA / STA Armoured Fire Resistant Power Cable

 China SWA / STA Armoured Fire Resistant Power Cable supplier

SWA / STA Armoured Fire Resistant Power Cable image

Get a Quote Email to us

Brand Name :
SHANCABLE

Model Number :
NH-YJV22

Certification :
CE/KEMA/ISO/PCCC

Place of Origin :
SHANGHAI,CHINA

MOQ :
200m

Price :
USD0.03-50 per meter

Supply Ability :
10KM per Week

Delivery Time :
As per requirement

Packaging Details :
100m/roll or customized

Function :
Fire Resistant

Screen :
Mica Tape

Rated Voltage :
600/1000V

Insulation :
PVC or XLPE

Sample :
Free

Number of cores :
1,2,3,4,5

Application :
Power Station

1.5-800mm2 ,NYY N2XY NYCY Fire Resistant Power Cable 0.6/1kV SWA/STA Armoured

Applications

Distribution and signal power cable for static outdoor application ( with protection against direct UV-irradiation ), in ground, in water, within facilities, in cable canals, in concrete, in conditions where heavier mechanical loads and specially tensile strains, are not expected.

Constructions

Conductor: Class 1/2 Plain annealed copper wires, solid or stranded, with mica tape wound

Insulation: XLPE or LSZH compound

Sheath: LSZH compound

Core color: red, black, blue, white for active core, green/yellow for earth core, orange or red or black for sheath

Max. Operating Temperature :100 meters per roll or wooden drum or as per requirement

Production Capacity :20 kilometer/ day

MOQ : 5000 meters for small size, 1000 meters for big size

Certificates

CE, RoHS, CCC, KEMA and more others at request

Standards

International: IEC 60502, IEC 60227 IEC 60331, IEC 601034

China: GB/T 12706-91 GB306.1-2001, GB/T18380.3-2001

Other standards such as BS,DIN and ICEA upon request

Technical data

Rated voltage: 0.6-KV

Max. Conductor Temp.: normal (90°C), short circuit no more than 5 s (the highest temperature of conductor shall no more than 250°C )

Min. Ambient Temp.:The cable shall be pre heated if the ambient temperature is below 0°C

Min. Bending Radius: single core cable 20(d+D)±5%

Multi-core cable 15(d+D)±5%

Rated Voltage: 0.6/1KV

Range of Nominal cross section: 1 core: 1.5 mm2 ~ 300 mm2 Multi core: 0.75 mm2 ~ 35 mm2

Operating characteristics

1. Max Long-time operating temperature of PVC insulated cable is 70°C,XLPE 90°C;

2. Installing temperature of cable should not be less than 0°C;

3. Max short-circuit temperature is:PVC not exceed 160°C,XLPE 250°C,Not more than5 Sec;

4. Permitting bending radius cable: Not less than 10 D times (D:external diameter of cable)

5. Perfect chemical stability, resistant against acids, alkali, grease and organic solvents, and flamer retardant.

Packaging:

Material:

Steel wooden drum (fumigation)

Cable length in each drum: 500m/1000m or as per actual cable length requirements.

Drum size:

As per cable length and container size