Power Transmission AAC All Aluminum Conductor High Voltage Overhead Bare Conductor
Power Transmission AAC All Aluminum Conductor High Voltage Overhead Bare Conductor image
Brand Name :
TANO CABLE
Model Number :
AAC
Certification :
CE, ISO,CCC
Place of Origin :
CHINA
MOQ :
2000 M
Payment Terms :
L/C, T/T, Western Union
Supply Ability :
100 tons per week
Delivery Time :
7-15 days
Packaging Details :
wooden drum, steel wooden drum, by roll, steel drum
Warranty :
2 years
Package :
Wooden drum
OEM :
Yes
Cable Type :
Bare Conductor
brand :
TANO CABLE
certification :
CE, ISO,CCC
TANO CABLE Good Quliaty All aluminum conductor high voltage AAC cable Overhead Use
Applications
Conductor(AAC,AAAC and ACSR) electronic cable have been widely used in power transmission lines with various voltage levels,because they have such good characteristics as simple structure,convenient installation and maintenance,low cost large transmission capacity.And they are also suitable for laying across rivers valleys and the places where special geographical features exist.
Service Performance
1.The permissible long-time operating temperature for aerial conductor cable is 70℃.
2.Under the circumstance that rare climate is occuring and ice coverage rate low in heavy ice area,the biggest stress of cable at the lowest point of the sag should not exceed 60% of the short-time destructive power.
3.When connecting conductors,the AAC conductor electronic cable beside the connecting tube cant be prominent.Otherwise,the force on the operating conductors will be unbalanced.After connectors are install,the connecting tube should be painted by moisture-proof varnish in order to protect it from corrosion.
4.Under installaion,the arc downing stress of all the conductors should be the same.With in the permissible distance of crossing buildings or dropping to the ground,the stress can be 10-15% higher than regular stress.
Material Standard
1.The hard aluminum conductor used for AAC and ACSR conforms to the standard GB/T 17048-1997(equivalent to IEC 60889:1987).
2.The zinc coated steel wire used for ACSR conforms to IEC 60888:1987.
3.Electronic cable can be arranged according to customers requirements for material standard,etc.
Construction of All Aluminum Conductor and Aluminum Conductor Steel Reinforced
Technical Parameters
AAC Technical Characteristics Based on Standard DIN 48201 / DIN EN50182
Code number | Area | Number of wires | Wire diameter | Conductor diameter | Linear mass | Rated strength | D.C. resistance at 20oC |
mm2 | No. | mm | mm | kg/km | kN | Ω/km | |
16 | 15.9 | 7 | 1.7 | 5.1 | 43.4 | 3.02 | 1.7986 |
25 | 24.2 | 7 | 2.1 | 6.3 | 66.3 | 4.36 | 1.1787 |
35 | 34.4 | 7 | 2.5 | 7.5 | 93.9 | 6.01 | 0.8317 |
50 | 49.5 | 7 | 3 | 9 | 135.2 | 8.41 | 0.5776 |
50 | 48.3 | 19 | 1.8 | 9 | 132.9 | 8.94 | 0.5944 |
70 | 65.8 | 19 | 2.1 | 10.5 | 180.9 | 11.85 | 0.4367 |
95 | 93.3 | 19 | 2.5 | 12.5 | 256.3 | 16.32 | 0.3081 |
120 | 117 | 19 | 2.8 | 14 | 321.5 | 19.89 | 0.2456 |
Packing
Third Party Inspection
Certificates
Factory
We are China Power Transmission AAC All Aluminum Conductor High Voltage Overhead Bare Conductor manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Tags: AAC All Aluminum Conductor, AAC CABLE, aac wireFAST AND RELIABLE SERVICE FOR YOUR PROJECT
Contact our trained experts today to find your perfect power solution.
ASK A QUESTION© 2020 Galaxy Electric Country Code Sitemap Cable Cable Drum