Medium Voltage Screened Aerial Bundle Cable AS/NZS 3599.1(AL/XLPE /CWS/HDPE)
Three XLPE insulated screened cores are bundled around the galvanized steel wires in a right hand lay.
Three XLPE insulated screened cores are bundled around the galvanized steel wires in a right hand lay.
1.Phase Conductor:Circular compacted stranded H68 aluminium to BS2627.
2.Conductor Screen:Extruded semi-conductive layer.
3.Insulation:XLPE.
4.Insulation Screen:Extruded semi-conductive layer.
5.Metallic Screen:Copper wire screen.
6.Separator:Semi-conductive swellable tape.
7.Outer Sheath:HDPE.
8.Support Conductor:Galvanized steel wires.
9.Assembly:Three XLPE insulated screened cores are bundled around the galvanized steel wires in a right hand lay.
AS/NZS 3599.1
Get all the answers to the most frequently asked questions (FAQs) regarding Aerial Bundle Cable 6.35/11kV & 12.7/22kV Medium Voltage Screened chart,Aerial Bundle Cable 6.35/11kV & 12.7/22kV Medium Voltage Screened sizes,Aerial Bundle Cable 6.35/11kV & 12.7/22kV Medium Voltage Screened full form,Aerial Bundle Cable 6.35/11kV & 12.7/22kV Medium Voltage Screened ampacity,Aerial Bundle Cable 6.35/11kV & 12.7/22kV Medium Voltage Screened diameter,Aerial Bundle Cable 6.35/11kV & 12.7/22kV Medium Voltage Screened manufacturers and much, much more.
Aerial Bundle Cable manufactured by GE Cable meets or exceeds the requirements of all international standards like ASTM, AS, BS, CSA, DIN, IEC, NFC, SS -etc
number of cores x nominal cross section | Nominal conductor diameter | Nominal insulation thickness | Nominal insulation screen thickness | Copper wire screen stranding | Nominal sheath thickness | Galvanized steel wire stranding | Nominal overall diameter | Weight | Continuous current rating, A | ||
---|---|---|---|---|---|---|---|---|---|---|---|
Still air | 1m/s wind | 2m/s wind | |||||||||
mm^2 | mm | mm | mm | No/mm | mm | No/mm | mm | kg/km | A | A | A |
Light duty screen | |||||||||||
3x35 | 6.9 | 3.4 | 0.8 | 25/0.85 | 1.8 | 7/2.00 | 54.1 | 1820 | 99 | 140 | 165 |
3x35 | 6.9 | 3.4 | 0.8 | 25/0.85 | 1.8 | 19/2.00 | 58.1 | 2130 | 100 | 145 | 165 |
3x50 | 8.1 | 3.4 | 0.8 | 25/0.85 | 1.8 | 19/2.00 | 60.4 | 2300 | 120 | 170 | 200 |
3x70 | 9.7 | 3.4 | 0.8 | 25/0.85 | 1.8 | 19/2.00 | 63.6 | 2570 | 150 | 215 | 250 |
3x95 | 11.4 | 3.4 | 0.8 | 25/0.85 | 1.8 | 19/2.00 | 67.0 | 2900 | 180 | 260 | 305 |
3x120 | 12.8 | 3.4 | 0.8 | 25/0.85 | 1.8 | 19/2.00 | 69.8 | 3190 | 205 | 300 | 355 |
3x150 | 14.2 | 3.4 | 0.8 | 25/0.85 | 1.9 | 19/2.00 | 73.0 | 3530 | 235 | 340 | 400 |
3x185 | 15.7 | 3.4 | 0.8 | 25/0.85 | 1.9 | 19/2.00 | 76.0 | 3890 | 265 | 390 | 460 |
Heavy duty screen | |||||||||||
3x35 | 6.9 | 3.4 | 0.8 | 40/0.85 | 1.8 | 7/2.00 | 54.1 | 2050 | 99 | 140 | 165 |
3x35 | 6.9 | 3.4 | 0.8 | 40/0.85 | 1.8 | 19/2.00 | 58.1 | 2360 | 100 | 145 | 165 |
3x50 | 8.1 | 3.4 | 0.8 | 23/1.35 | 1.8 | 19/2.00 | 62.4 | 2820 | 120 | 175 | 200 |
3x70 | 9.7 | 3.4 | 0.8 | 32/1.35 | 1.8 | 19/2.00 | 65.6 | 3440 | 150 | 215 | 250 |
3x95 | 11.4 | 3.4 | 0.8 | 39/1.35 | 1.8 | 19/2.00 | 69.0 | 4030 | 180 | 260 | 305 |
3x120 | 12.8 | 3.4 | 0.8 | 39/1.35 | 1.8 | 19/2.00 | 71.8 | 4320 | 205 | 300 | 355 |
3x150 | 14.2 | 3.4 | 0.8 | 39/1.35 | 1.9 | 19/2.00 | 75.0 | 4670 | 230 | 340 | 400 |
3x185 | 15.7 | 3.4 | 0.8 | 39/1.35 | 1.9 | 19/2.00 | 78.0 | 5020 | 265 | 390 | 460 |
number of cores x nominal cross section | Nominal conductor diameter | Nominal insulation thickness | Nominal insulation screen thickness | Copper wire screen stranding | Nominal sheath thickness | Galvanized steel wire stranding | Nominal overall diameter | Weight | Continuous current rating, A | ||
---|---|---|---|---|---|---|---|---|---|---|---|
Still air | 1m/s wind | 2m/s wind | |||||||||
mm^2 | mm | mm | mm | No/mm | mm | No/mm | mm | kg/km | A | A | A |
Light duty screen | |||||||||||
3x35 | 6.9 | 5.5 | 0.8 | 25/0.85 | 1.8 | 7/2.00 | 62.7 | 2280 | 100 | 140 | 165 |
3x35 | 6.9 | 5.5 | 0.8 | 25/0.85 | 1.8 | 19/2.00 | 66.7 | 2580 | 105 | 145 | 165 |
3x50 | 8.1 | 5.5 | 0.8 | 25/0.85 | 1.8 | 19/2.00 | 69.0 | 2780 | 125 | 170 | 200 |
3x70 | 9.7 | 5.5 | 0.8 | 25/0.85 | 1.9 | 19/2.00 | 72.6 | 3110 | 150 | 215 | 250 |
3x95 | 11.4 | 5.5 | 0.8 | 25/0.85 | 1.9 | 19/2.00 | 76.0 | 3460 | 180 | 260 | 300 |
3x120 | 12.8 | 5.5 | 0.8 | 25/0.85 | 2.0 | 19/2.00 | 79.2 | 3810 | 205 | 300 | 350 |
3x150 | 14.2 | 5.5 | 1.0 | 25/0.85 | 2.0 | 19/2.00 | 82.8 | 4230 | 230 | 340 | 395 |
3x185 | 15.7 | 5.5 | 1.0 | 25/0.85 | 2.1 | 19/2.00 | 86.2 | 4650 | 265 | 390 | 450 |
Heavy duty screen | |||||||||||
3x35 | 6.9 | 5.5 | 0.8 | 40/0.85 | 1.8 | 7/2.00 | 62.7 | 2510 | 100 | 140 | 165 |
3x35 | 6.9 | 5.5 | 0.8 | 40/0.85 | 1.8 | 19/2.00 | 66.7 | 2810 | 105 | 145 | 165 |
3x50 | 8.1 | 5.5 | 0.8 | 23/1.35 | 1.8 | 19/2.00 | 71.0 | 3300 | 125 | 175 | 200 |
3x70 | 9.7 | 5.5 | 0.8 | 32/1.35 | 1.9 | 19/2.00 | 74.6 | 3970 | 155 | 215 | 250 |
3x95 | 11.4 | 5.5 | 0.8 | 39/1.35 | 1.9 | 19/2.00 | 78.0 | 4600 | 180 | 260 | 305 |
3x120 | 12.8 | 5.5 | 0.8 | 39/1.35 | 2.0 | 19/2.00 | 81.2 | 4950 | 205 | 300 | 350 |
3x150 | 14.2 | 5.5 | 1.0 | 39/1.35 | 2.0 | 19/2.00 | 84.8 | 5360 | 230 | 340 | 395 |
3x185 | 15.7 | 5.5 | 1.0 | 39/1.35 | 2.1 | 19/2.00 | 88.2 | 5790 | 265 | 390 | 450 |