Low Voltage XLPE Insulated Power Cable 21/35(36)Kv Abrasion Resistance

 China Low Voltage XLPE Insulated Power Cable 21/35(36)Kv Abrasion Resistance supplier

Low Voltage XLPE Insulated Power Cable 21/35(36)Kv Abrasion Resistance image

Get a Quote Email to us

Brand Name :
SHANCABLE

Model Number :
YJLV 0.6-1KV

Certification :
ISO,CE,IEC,TUV,KEMA

Place of Origin :
Shanghai, China

MOQ :
Negotiable

Price :
Negotiable

Payment Terms :
L/C, T/T

Supply Ability :
100KM/Week

Delivery Time :
10 Days

Packaging Details :
Wooden Drum

Type :
XLPE Insulated Power Cable

Feature :
Low Voltage

Conductor Screen :
Semi-conductor

Sample :
Free

Insulation Color :
Yellow,Blue

Advnatage :
Abrasion Resistance

Sheath :
PVC or FR-PVC type ST2 to IEC 60502, black

Screen :
Copper tape

Low Voltage XLPE Insulated Power Cable 21/35(36)Kv Abrasion Resistance

XLPE Insulated Power Cable Applications

The product is used in power transmission and distribution line at voltage up. It does not only have excellent electric, mechanical properties, but also has powerful resistance against chemical corrosion, heat aging and environmental stress.

XLPE Insulated Power Cable Construction

Conductor : Compact stranded Aluminum conductor, Cl.2 as per IEC 60228

Insulation : XLPE (cross-linked polyethylene) rated at 90 OC

Sheath : PVC or FR-PVC type ST2 to IEC 60502, black


XLPE Insulated Power Cable Standards

International: IEC 60502-1, IEC 60228,

China: GB/T 12706, (GB/T 18380-3 for ZR-YJLV only)

Other standards such as BS,DIN and ICEA upon request


XLPE Insulated Power Cable Technical data

Rated voltage: 21/35(36)kV

Maximum Conductor Temperature: under normal (90 OC), emergency (130OC) or short circuit no more than 5 s (250℃) conditions.

Min. Ambient Temp. 0 OC, after installation and only when cable is in a fixed position

Min. Bending Radius: 20 x cable O.D for single core

15 x cable O.D for multi core

XLPE Insulated Power Cable Specifications

Nom. Cross-section of conductor Strands No./Dia. Of Conductor Insulation Thickness Sheath Thickness Approx. O.D.

Approx.

Weight

Max. D.C Resistance of Conductor (20 ℃) Testing Voltage A.C Current Rating
mm2 pc/mm mm mm (mm) kg/km Ω /km kV/5min In air (A) In soil(A)
4 × 4 1/2.25 0.7 1.8 13.0 155 7.41 3.5 27 36
4 × 6 1/2.76 0.7 1.8 14.0 184 4.61 3.5 35 46
4 × 10 7/1.38 0.7 1.8 17.0 258 3.08 3.5 47 59
4 × 16 7/1.78 0.7 1.8 20.0 366 1.91 3.5 64 80
4 × 25 7/2.14 0.9 1.8 23.0 540 1.200 3.5 82 100
4 × 35 7/2.52 0.9 1.8 25 686 0.868 3.5 100 120
4 × 50 10/2.52 1.0 1.8 23 907 0.641 3.5 125 145
4 × 70 14/2.52 1.1 1.8 27 1192 0.443 3.5 155 175
4 × 95 19/2.52 1.1 1.9 31 1598 0.320 3.5 200 210
4 × 120 24/2.52 1.2 2.0 33 1949 0.253 3.5 220 240
4 × 150 30/2.52 1.4 2.2 38 2517 0.206 3.5 250 270
4 × 185 37/2.52 1.6 2.3 42 3091 0.1640 3.5 295 305
4 × 240 48/2.52 1.7 2.5 47 3825 0.1250 3.5 345 355
4 × 300 61/2.52 1.8 2.6 52 4830 0.1000 3.5 395 400
4 × 400 61/2.97 2.0 3.1 66 5840 0.0778 3.5 445 445