Indoor Embedded 12KV Vacuum AC Circuit Breaker

 China Indoor Embedded 12KV Vacuum AC Circuit Breaker supplier

Indoor Embedded 12KV Vacuum AC Circuit Breaker image

Get a Quote Email to us

Brand Name :
Suntech

Model Number :
VF(R)-12

Certification :
ISO

Place of Origin :
Ningbo,China

MOQ :
1 PCS

Price :
Get newest price

Payment Terms :
L/C , T/T, Western Union

Supply Ability :
20000 pcs per month

Delivery Time :
30 days after Payment

Packaging Details :
Exported cartons or cases

Type :
Vacuum Circuit Breaker

Poles Number :
3

Ambient temperature :
-40°C-+40°C

Altitude :
≤1000m

New Generation Indoor Embedded High Voltage Vacuum AC Circuit Breaker

VF(R)-12 indoor embedded high-voltage alternating-current vacuum load switch-fuse combination (“vacuum load switch" )is a new generation vacuum switching equipment developed based on unique design ideas to meet the market demand. It is widely used for indoor armored air-insulated switch cabinets. In normal conditions, it can operate within its technical parameters in any grid of the specified voltage level safely and stably.

Item Unit Reference value

VF-12/T630-20

Vacuum load

switch

VFR-12/T125-50

Vacuum load

switch-fuse

combination

VFH-12/T630-25

High breaking

capacity vacuum

switch

VFHR-12/T125-50

High breaking

capacity vacuum

switch-fuse

combination

Rated voltage kV 12 12 12 12
Rated insulation level Lightning impuse withstand voltage kV 75 75 75 75
1min power-frequency withstand voltage kV 42 42 42 42
Rated frequency Hz 50/60 50/60 50/60 50/60
Rated current A 630 125(fuse) 630 125(fuse)

Rated short-circuit

breaking current

kA 50(fuse) 25 25

Rated short- circuit

making current (peak value)

kA 50 63

Rated short-time

withstand current

kA 20 25

Rated withstand current

(peak value)

kA 50 63

Rated breaking current of

cable during charge

A 16

Rated breaking current of

no-load transformer

kVA 1250 1250

Rated breaking

take-over current

A 3150 3150

Breaking times of

the rated short-circuit current

Times
Mechanical life M2 level M2 level M2 level M2 level
Weight kg 125

ransformer capacity and fuse selection

1. The fuse can cut off a large short-circuit current in less than 10 ms and its breaking current can be up to 50KA. Thus, it can protect the transformer most efectively.

2. In terms of match between the transformer and the fuse (Table 1), the potential surge current of the fuse must be considered. Thus, fusing current of the fuse must be 1.6 times of the rated value; designer must consider possible fluctuations of other parameters of the grid and reserve margins for them. If a fuse is selected for high-voltage motor protection, designer must consider frequency of start of the high-voltage motor because frequent starts of the high-voltage motor will result in the fuse's failure when timely cooling is not available.

Primary voltage of

the transformer(kV)

Capacity of

the transformer(kVA)

Model of the fuse

Rated current

of the fuse(A)

Model for

the domestic market

Model for

international market

6.6 200 XRNT-10 12kV BDGHC 31.5
250 40
300/315 50
400 12kV BDGHC 63
500 80
630 90

Standard

1. GB 3804-2004 High-voltage load alternating-current switches for rated voltage above 3.6 kV and less than 40.5 kV

2. GB 16926-2009 High-voltage load alternating- current switch-fuse combinations

Operating conditions

1. Ambient temperature: – 40℃-+40℃ (below 35℃ within 24 hours)

2. Relative humidity:≤95% (daily average) or≤90% (monthly average)

3. Altitude: ≤1000m

We are China Indoor Embedded 12KV Vacuum AC Circuit Breaker manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.