DIN EN 60228 class 2 Fire Resistant Cable 0°C to 90°C Operating Temperature
DIN EN 60228 class 2 Fire Resistant Cable 0°C to 90°C Operating Temperature image
Brand Name :
SHANCABLE
Model Number :
WDZA-YJY
Certification :
KEMA,ISO,CE,IEC,PICC
Place of Origin :
SHANGHAI, CHINA
MOQ :
1000meters
Price :
US$1.0~120per meter
Payment Terms :
L/C, T/T
Supply Ability :
30Kilometer/Month
Delivery Time :
Depending on order quantity
Standard :
IEC502 & IEC332-3
Voltage (Uo/U) :
0.6/1kV
A.C Voltage :
3.5kV 5min
No. of Cores :
1,2,3,4,5
Operating Temperature :
0°C to 90°C
Sample :
Available
CU/XLPE/PVC 0.6/1kV Fire Retardant Fire Resistant FRC Power Cable
Our company can produce both flame retardant and non-flame retardant series of XLPE power cable.. Our products can be produced according to our works specifications which are equivalent to GB12706, IEC60502, IEC60332, IEC60754, and its some indexes are superior to standards stated above..
The flame-retardant cable covers all kinds of low-smoke low-halogen, low-smoke halogen free and three classes of A, B, C. We can design and manufacture special XLPE cable according to the other standards require by the customers, such as heavy section cut part conductors, water-resistant, defend termites, defend mouse, and so on..
Main properties
No | Test item | Property | |||
1 | Construction | Listed to the tables | |||
2 | Conductor resistance | Listed to the tables | |||
3 | Voltage test | A.C 3.5kV 5min | No breaken | ||
4 | Mechanical properties before aging | Tensile strength | Insulation | Min.12.5N/mm² | |
Sheath | Min.12.5N/mm² | ||||
Elongation at break | Insulation | Min.150% | |||
Sheath | Min.150% | ||||
Mechanical properties after aging | Tensile strength | Insulation |
100°C±2°C 7days Min.±12.5N/mm² |
||
Sheath |
100°C±2°C 7days Min.±12.5N/mm² |
||||
Varying valve of tensile strength | Insulation |
100°C±2°C 7days Min.±25% |
|||
Sheath |
100°C±2°C 7days Min.±25% |
||||
Elongation at break | Insulation |
100°C±2°C 7days Min.±150% |
|||
Sheath |
100°C±2°C 7days Min.±150% |
||||
Varying valve of tensile strength | Insulation |
100°C±2°C 7days Min.±25% |
|||
Sheath |
100°C±2°C 7days Min.±25% |
||||
5 | Flame-retardant property | Comply with GB12666.5-90(CB) and IEC332-3(CB) | |||
6 | Constant of insulation resistivity | Min at 20°C | 36.7 | ||
Ki MΩ.km | Min at 70°C | 0.037 |
Standards:
IEC 60502, 60332, 60331
DIN VDE 0276-620
HD 620 S1: 1996
DIN EN 60228 class 2 (construction)
Model Explanation:
Model | Nominal Cross Section (mm2) | ||||
Single Core |
Two Core |
Three Core |
Four Core |
Five Core |
|
NH-VV NH-YJV | 1.5-800 | 1.5-800 | 1.5-800 | 1.5-800 | 1.5-800 |
NH-VV22 NH-YJV22 | 6-400 | 4-300 | 4-300 | 4-300 | 4-300 |
NH-VV32 NH-YJV32 | 10-800 | 4-300 | 4-300 | 4-300 |
4-300 |
FAQ
Q: | How long does it take to get a quote back? |
A: | Most quotes are returned within 24 hours, however, if it is for a special construction, it could take more days. |
Q: | Do you custom package? |
A: | We strive to meet our customers' needs and therefore have no problem meeting most specifications. We can reel into coils, disposable cartons, special reels, or load your wire and cable into reusable plastic containers. Please check with your sales representative first to verify we can meet your need. |
Q: | What warranties do your products carry? |
A: | SHAN cable guarantees that all of our products, wires cables,and more are free from defects. We will take back any product that does not meet the agreed quality by both parties. |
Q: | Do you sell other products besides wire and cable? |
A: | Wire and cable is our forte, however, we also sell connectors, cable assemblies and cable tools to name just a few. Our products serve numerous markets all over the world |
We are China DIN EN 60228 class 2 Fire Resistant Cable 0°C to 90°C Operating Temperature manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Tags: Fire Resistant Cable, fire retardant cable, flame resistant cable