ACSR With Aluminum & Steel Conductor According To IEC 61089 Standard (AAC,AAAC,ACSR)
ACSR With Aluminum & Steel Conductor According To IEC 61089 Standard (AAC,AAAC,ACSR) image
ACSR With Aluminum & Steel Conductor According To IEC 61089 Standard (AAC,AAAC,ACSR)
Application:
ACSR conductors are widely used for electrical power transmission over long distances, since they are ideal for long overhead lines spans. They are also used as a messenger for supporting overhead electrical cables.
Construction:
ACSR conductors are formed by several wires of aluminium and galvanized steel, stranded in concentric layers. The wire or wires which form the core, are made of galvanized steel and the external layer or layers, are of aluminium. Galvanized steel core consist normally of 1, 7 or 19 wires. The diameters of steel and aluminium wires can be the same, or different.
By varying the relative proportions of aluminium and steel, the required characteristics for any particular application can be reached. A higher U. T. S. Can be obtained, by increasing steel content, and a higher current carrying capacity by increasing aluminium content.
Electrical properties:
density@20ºC | Aluminium: 2.703 kg/dm |
Galvanised Steel: 7.80 kg/dm | |
Temperature Coefficient@20°C | Aluminium: 0.00403 (°C) |
resistivity@20°C | Aluminium: Should not exceed 0.028264 |
linear Expansivity |
Aluminium: 23 x10 (°C) |
Galvanised Steel: 11.5 x10 (1/°C) |
SERVICE CONDITIONS
Ambient Temperature | -5°C – 50°C |
Wind Pressure | 80 – 130kg/m |
Seismic Acceleration | 0.12 – 0.05g |
Isokeraunic level | 10 – 18 |
relative Humidity | 5 – 100% |
ACSR With Aluminum & Steel Conductor According To IEC 61089 Standard (AAC,AAAC,ACSR)technical data sheet:
Numbers of Wires | Modules of Elasticity | Coeficient of linear Expansion | |||
AL | STEEL | Kg/mm2 | Lb/in2 | 1/Cº | 1/Fº |
6 | 1 | 81 | 11.5 x106 | 19.1 x10-6 | 10.6 x10-6 |
6 | 7 | 77 | 11.0 x106 | 19.8 x10-6 | 11.0 x10-6 |
12 | 7 | 107 | 15.2 x106 | 15.3 x10-6 | 8.5 x10-6 |
18 | 1 | 67 | 9.5 x106 | 21.2 x10-6 | 11.8 x10-6 |
24 | 7 | 74 | 10.5 x106 | 19.6 x10-6 | 10.9 x10-6 |
26 | 7 | 77 | 10.9 x106 | 18.9 x10-6 | 10.5 x10-6 |
28 | 7 | 79 | 11.2 x106 | 18.4 x10-6 | 10.2 x10-6 |
30 | 7 | 82 | 11.6 x106 | 17.8 x10-6 | 9.9 x10-6 |
30 | 19 | 80 | 11.4 x106 | 18.0 x10-6 | 10.0 x10-6 |
32 | 19 | 82 | 11.7 x106 | 17.5 x10-6 | 9.7 x10-6 |
54 | 7 | 70 | 9.9 x106 | 19.3 x10-6 | 10.7 x10-6 |
54 | 19 | 68 | 9.7 x106 | 19.4 x10-6 | 10.8 x10-6 |
CONSTRUCTION PARAMETERS
• IEC 60189
Code | Nominal Area | Stranding | Overall Diameter | Weight | Breaking Load | Electrical Resistance @20° | Current Rating* | |||
AL | STEEL | TOTAL | AL | STEEL | ||||||
mm2 | mm2 | mm2 | No.xmm | No.xmm | mm | Kg/Km | KN | Ω/Km | A | |
16 | 16 | 2.67 | 18.7 | 6/1.84 | 1/1.84 | 5.52 | 64.6 | 6.08 | 1.7934 | 85 |
25 | 25 | 4.17 | 29.2 | 6/2.30 | 1/2.30 | 6.9 | 100.9 | 9.13 | 1.1478 | 112 |
40 | 40 | 6.67 | 46.7 | 6/2.91 | 1/2.91 | 8.73 | 161.5 | 14.4 | 0.7174 | 150 |
63 | 63 | 10.5 | 73.5 | 6/3.66 | 1/3.66 | 10.98 | 254.4 | 21.63 | 0.4555 | 198 |
100 | 100 | 16.7 | 117 | 6/4.61 | 1/4.61 | 13.83 | 403.8 | 34.33 | 0.2869 | 263 |
125 | 125 | 6.94 | 132 | 18/2.97 | 1/2.97 | 14.85 | 397.9 | 29.17 | 0.2304 | 299 |
125 | 125 | 20.4 | 145 | 26/2.47 | 7/1.92 | 15.64 | 503.9 | 45.69 | 0.231 | 302 |
160 | 160 | 8.89 | 169 | 18/3.36 | 1/3.36 | 16.8 | 509.3 | 36.18 | 0.18 | 347 |
160 | 160 | 26.1 | 186 | 26/2.80 | 7/2.18 | 17.74 | 644.9 | 57.69 | 0.1805 | 351 |
200 | 200 | 11.1 | 211 | 18/3.76 | 1/3.76 | 18.8 | 636.7 | 44.22 | 0.144 | 398 |
200 | 200 | 32.6 | 233 | 26/3.13 | 7/2.43 | 19.81 | 806.2 | 70.13 | 0.1444 | 402 |
250 | 250 | 24.6 | 275 | 22/3.80 | 7/2.11 | 21.53 | 880.6 | 68.72 | 0.1154 | 458 |
250 | 250 | 40.7 | 291 | 26/3.50 | 7/2.72 | 22.16 | 1007.7 | 87.67 | 0.1155 | 461 |
315 | 315 | 21.8 | 337 | 45/2.99 | 7/1.99 | 23.91 | 1039.6 | 79.03 | 0.0917 | 526 |
315 | 315 | 51.3 | 366 | 26/3.93 | 7/3.05 | 24.87 | 1269.7 | 106.83 | 0.0917 | 530 |
400 | 400 | 27.7 | 428 | 45/3.36 | 7/2.24 | 26.88 | 1320.1 | 98.36 | 0.0722 | 607 |
400 | 400 | 51.9 | 452 | 54/3.07 | 7/3.07 | 27.63 | 1510.3 | 123.04 | 0.0723 | 610 |
450 | 450 | 31.1 | 481 | 45/3.57 | 7/2.38 | 28.56 | 1485.2 | 107.47 | 0.0642 | 651 |
450 | 450 | 58.3 | 508 | 54/3.26 | 7/3.26 | 29.34 | 1699.1 | 138.42 | 0.0643 | 655 |
500 | 500 | 34.6 | 535 | 45/3.76 | 7/2.51 | 30.09 | 1650.2 | 119.41 | 0.0578 | 693 |
500 | 500 | 64.8 | 565 | 54/3.43 | 7/3.43 | 30.87 | 1887.9 | 153.8 | 0.0578 | 697 |
560 | 560 | 38.7 | 599 | 45/3.98 | 7/2.65 | 31.83 | 1848.2 | 133.74 | 0.0516 | 741 |
560* | 560 | 70.9 | 631 | 54/3.63 | 19/2.18 | 32.68 | 2103.4 | 172.59 | 0.0516 | 745 |
630 | 630 | 43.6 | 674 | 45/4.22 | 7/2.81 | 33.75 | 2079.2 | 150.45 | 0.0459 | 794 |
630* | 630 | 79.8 | 710 | 54/3.85 | 19/2.31 | 34.65 | 2366.3 | 191.77 | 0.0459 | 798 |
710 | 710 | 49.1 | 759 | 45/4.48 | 7/2.99 | 35.85 | 2343.2 | 169.56 | 0.0407 | 851 |
710* | 710 | 89.9 | 800 | 54/4.09 | 19/2.45 | 36.79 | 2666.8 | 216.12 | 0.0407 | 856 |
800* | 800 | 34.6 | 835 | 72/3.76 | 7/2.51 | 37.61 | 2480.2 | 167.41 | 0.0361 | 910 |
800* | 800 | 66.7 | 867 | 84/3.48 | 7/3.48 | 38.28 | 2732.7 | 205.33 | 0.0362 | 912 |
800* | 800 | 101 | 901 | 54/4.34 | 19/2.61 | 39.09 | 3004.9 | 243.52 | 0.0362 | 916 |
900* | 900 | 38.9 | 939 | 72/3.99 | 7/2.66 | 39.9 | 2790.2 | 188.33 | 0.0321 | 972 |
900* | 900 | 75 | 975 | 84/3.69 | 7/3.69 | 40.59 | 3074.2 | 226.5 | 0.0322 | 974 |
1000* | 1000 | 43.2 | 1043 | 72/4.21 | 7/2.80 | 42.08 | 3100.3 | 209.26 | 0.0289 | 1031 |
1120* | 1120 | 47.3 | 1167 | 72/4.45 | 19/1.78 | 44.5 | 3464.9 | 234.53 | 0.0258 | 1096 |
1120* | 1120 | 91.2 | 1211 | 84/4.12 | 19/2.47 | 45.31 | 3811.5 | 283.17 | 0.0258 | 1100 |
1250* | 1250 | 102 | 1352 | 84/4.35 | 19/2.61 | 47.85 | 4253.9 | 316.04 | 0.0232 | 1165 |
1250* | 1250 | 52.8 | 1303 | 72/4.70 | 19/1.88 | 47 | 3867.1 | 261.75 | 0.0231 | 1163 |
1120* | 1120 | 91.2 | 1211 | 84/4.12 | 19/2.47 | 45.31 | 3811.5 | 283.17 | 0.0258 | 1100 |
Why you choose us?
- OEM/ODM services provided;
- Products comply with GB, IEC, BS, ASTM, DIN, VDE and JIS standards; Customer standard requirments Accepted;
- Certified to ISO 9001:2015, ISO 14001:2015 and OHSAS 18001:2007;
- Registered capital of $30 million and factory covers an area of 60,000㎡;
- Advanced test equipment and procedures, 100% inspection before factory;
- Enough stocks and the higest efficient shipping time guarranteed;
- Professional pre-sales and after-sales services provided.
We are China ACSR With Aluminum & Steel Conductor According To IEC 61089 Standard (AAC,AAAC,ACSR) manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Tags: ACSR Aluminum Conductor Steel Reinforced, Aluminum Conductor Steel Reinforced, overhead line Conductor