AAC Aluminum Conductor Electronic Cable Code 630sqmm DIN / IEC Standard
AAC Aluminum Conductor Electronic Cable Code 630sqmm DIN / IEC Standard image
AAC Aluminum Conductor electronic cable Code 630sqmm With High Strength DIN / IEC Standard(AAC,AAAC, ACSR)
APPLICATION
Conductor (AAAC, AAAC and ACSSR) electronic cable have been widely used in power transmission lines with various voltage levels, because they such good characteristics as simple structure, convenient installation and maintenance, low cost large transmission capacity. And they are also suitable for laying across rivers valleys and the place where special geographical features exist.
SERVICE PERFORMANCE
- The permissible long-time operating temperature for aerial conductor cable is 70°C.
- Under the circumstance that rare climate is occurring and ice coverage rate low in heavy ice area, the biggest stress of cable at the lowest point of sag should not exceed 60% of the short-time destructive power.
- When connecting conductors, the AAC conductor electronic cable beside the connecting tube can’t be prominent. Otherwise, the force on the operating conductors will be unbalanced. After connectors are install, the connecting tube should be painted by moisture-proof varnish in order to it from corrosion.
- Under installation, the arc downing stress of all conductors should be the same. With in the permissible distance of the crossing buildings or dropping to the ground, the stress can be 10-15% higher than regular stress.
MATERIAL STANDARD
1. The hard aluminum conductor used for AAC and ACSR conforms to the standard GB/T 17048-1997(equivalent to IEC 60889:1987).
2. The zinc coated steel wire used for ACSR conforms to IEC 60888:1987.
3. Electronic cable can be arranged according to the customers requirements for material standard, etc.
Construction of All Aluminum Conductor and Aluminum Conductor Steel Reinforced.
CHARACTERISTICS:
1. Simple construction;
2. Easy installation and maintenance;
3. Lower price and large transmission capacity;
4. Better for long distance power transmission;
ELECTRICAL PROPERTIES:
Density@20℃ | 2.703 kg/dm |
Temperature Coefficient@20°C | 0.00403 (°C) |
Resistivity@20°C | 0.028264 |
Linear Expansivity | 23 x10-6 (°C |
SERVICE CONDITIONS:
Ambient Temperature | -5°C – 50°C |
Wind Pressure | 80 – 130kg/m2 |
Seismic Acceleration | 0.12 – 0.05g |
Isokeraunic Level | 10 – 18 |
Relative Humidity | 5 – 100% |
Density@20℃ | 2.703 kg/dm |
Temperature Coefficient@20°C | 0.00403 (°C) |
Resistivity@20°C | 0.028264 |
Linear Expansivity | 23 x10-6 (°C) |
Overhead AAC Aluminum Conductor Cable With High Strength DIN / IEC Standard(AAC,AAAC, ACSR) CONSTRUCTION PARAMETERS:
IEC 61089
CODE |
Nominal Area |
Stranding |
Overall Diameter |
Weight |
Rated Strength |
Electrical Resistance |
Current Rating* |
mm2 | No.×mm | mm | Kg/Km | KN | Ω/Km | A | |
10 | 10 | 7/1.35 | 4.05 | 27.4 | 1.95 | 2.8633 | 62 |
16 | 16 | 7/1.71 | 5.13 | 43.8 | 3.04 | 1.7896 | 84 |
25 | 25 | 7/2.13 | 6.39 | 68.4 | 4.5 | 1.1453 | 110 |
40 | 40 | 7/2.70 | 8.1 | 109.4 | 6.8 | 0.7158 | 147 |
63 | 63 | 7/3.39 | 10.17 | 172.3 | 10.39 | 0.4545 | 195 |
100 | 100 | 19/2.59 | 12.95 | 274.8 | 17 | 0.2877 | 259 |
125 | 125 | 19/2.89 | 14.45 | 343.6 | 21.25 | 0.2302 | 297 |
160 | 160 | 19/3.27 | 16.35 | 439.8 | 26.4 | 0.1798 | 345 |
200 | 200 | 19/3.66 | 18.3 | 549.7 | 32 | 0.1439 | 396 |
250 | 250 | 19/4.09 | 20.45 | 687.1 | 40 | 0.1151 | 454 |
315 | 315 | 37/3.29 | 23.03 | 867.9 | 51.97 | 0.0916 | 522 |
400 | 400 | 37/3.71 | 25.97 | 1102 | 64 | 0.0721 | 603 |
450 | 450 | 37/3.94 | 27.58 | 1239.8 | 72 | 0.0641 | 647 |
500 | 500 | 37/4.15 | 29.05 | 1377.6 | 80 | 0.0577 | 688 |
560 | 560 | 37/4.39 | 30.73 | 1542.9 | 89.6 | 0.0515 | 736 |
630 | 630 | 61/3.63 | 32.67 | 1738.3 | 100.8 | 0.0458 | 789 |
710 | 710 | 61/3.85 | 34.65 | 1959.1 | 113.6 | 0.0407 | 845 |
800 | 800 | 61/4.09 | 36.81 | 2207.4 | 128 | 0.0361 | 905 |
900 | 900 | 61/4.33 | 38.97 | 2483.3 | 144 | 0.0321 | 967 |
1000 | 1000 | 61/4.57 | 41.13 | 2759.2 | 160 | 0.0289 | 1026 |
1120 | 1120 | 91/3.96 | 43.56 | 3093.5 | 179.2 | 0.0258 | 1091 |
Product show
About Zhenglan Cable
- overhead power transmission use bare conductor(ACSR, AAC, etc)
- 1kv, 10kv, 35kv overhead power transmission use insulated conductor(single core covered cable, ABC cable)
- STA/SWA armored or unarmored PVC/XLPE/PE insulated LV(low voltage) power cable
- STA/SWA armored or unarmored XLPE insulated MV(medium voltage)power cable
- 450/750V instrument use control cable (shielded or unshielded)
- 300/300V, 300/500V, 450/750V fixed installation use building wire
If you are interested, please do not hesitate to contact us.Any inquiry will be welcomed.
We are China AAC Aluminum Conductor Electronic Cable Code 630sqmm DIN / IEC Standard manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Tags: 630sqmm Electronic Cable Conductor, Bare Aluminum Conductor, DIN Standard Aluminum Conductors, IEC Standard AAC Aluminum Conductor