Lead Sheath HV Power Cable 132 kV 1 × 800 mm2 , High Voltage XLPE Power Cable

 China Lead Sheath HV Power Cable 132 kV 1 × 800 mm2 , High Voltage XLPE Power Cable supplier

Lead Sheath HV Power Cable 132 kV 1 × 800 mm2 , High Voltage XLPE Power Cable image

Get a Quote Email to us

Brand Name :
Tano Cable

Model Number :
132kV HV power cable

Certification :
ISO

Place of Origin :
China

MOQ :
1000 Meters

Price :
Negotiable

Payment Terms :
L/C, T/T

Supply Ability :
10km per month

Delivery Time :
15-30 working days

Packaging Details :
By steel-wooden drum and steel drum with strong protection to suit for the long-distance delivery

Voltage :
76/132kV

Conductor :
Copper wire

Insulation :
XLPE

Jacket :
HDPE/MDPE

Armour :
Lead sheath

Packing :
Steel drum

TANO CABLE 132 kV 1 × 800 mm2 lead sheath High Voltage XLPE Power Cable

Construction of XLPE Power Cable

Conductor:Copper/Aluminium wire, stranded to BS 6360 class 2.
Conductor Screen: The conductor screen consists of an extruded layer of non metallic, semi-conducting compound applied on top of a semi-conducting tape. The conductor screen is applied under triple extrusion process over the conductor along with the insulation and the insulation screen. The extruded semi-conducting compound is firmly bonded to the insulation to exclude all air voids and can be easily hand stripped on site.

Insulation: Extruded cross-linked polyethylene (XLPE-GP8) compound insulation
Insulation Screen: The insulation screen consists of an extruded layer of non metallic, semi-conducting compound extruded over the insulation of each core. The extruded semi-conducting layer shall consist of bonded or cold strippable semi-conducting compound capable of removal for jointing or terminating.

Semi-conductive Water Blocking Swellable Tape: A semi-conducting tape shall be applied over the core assembly as a bedding for the metallic layer. The minimum thickness is 0.3 mm and the maximum resistivity is 500 Ohm-m at 90°C. The screen is tightly fitted to the insulation to exclude all air voids and can be easily hand stripped on site. The screen may be covered by semi-conductive water blocking swellable tape to ensure longitudinal watertightness.

Metallic Layer: The metallic layer may be applied over the core assembly collectively. The metallic screen shall consist of either copper tapes or a concentric layer of copper wires or a combination of tapes and wires.

Swellable Tape:Swellable material
Separation Sheath:Aluminum Tape sheath
Outer Sheath:Thermoplastic HDPE-ST3 compound

Construction Parameters

Conductor Thickness of Conductor Screen Approx. Thickness of Insulation Thickness of Insulation Screen Approx. Thickness of Lead Sheath Thickness of Outer Sheath Outer Diameter of Cable Weight of Cable Max. DC Conductor Resistance at 20 ℃ Capacitance
Cross-Sectional Area Shape Diameter
mm2 mm mm mm mm mm mm mm kg /m Ω/km μF/km
240 Compact Round
Stranded
18.1 1.5 16.0 1.3 2.4 4.5 76 11.2 0.0754 0.16
300 20.4 1.5 16.0 1.3 2.5 4.5 78 12.3 0.0601 0.17
400 23.2 1.5 16.0 1.3 2.6 4.5 81 13.8 0.0470 0.18
500 26.3 1.5 16.0 1.3 2.7 4.5 85 15.6 0.0366 0.20
630 30.2 1.5 16.0 1.3 2.7 4.5 88 17.5 0.0283 0.21
800 34.0 1.5 16.0 1.3 2.9 4.5 93 20.4 0.0221 0.23
1000 Segment Stranded
(Miliken)
38.7 1.5 16.0 1.3 3.0 4.5 98 23.6 0.0176 0.25
1200 41.8 1.5 16.0 1.3 3.1 4.5 102 26.5 0.0151 0.27
1600 48.1 1.5 16.0 1.3 3.3 4.5 108 31.7 0.0113 0.30
2000 54.3 1.5 16.0 1.3 3.5 4.5 115 37.7 0.0090 0.32
2500 63.0 1.5 16.0 1.3 3.7 4.5 123 44.3 0.0072 0.36