0.6/1 KV XLPE Insulated Cable Triplex Service Drop Aluminum Conductor
Triplex aluminum conductor cables: The triple center cable provides control dispersion for high voltage (HV) mains in mechanical and utility applications. Note that the red external sheath is prone to blurring when exposed to UV radiation, if that's not too much bother. Znergycable products outlast UL 1426, ABYC, and US Coast Guard Charter pontoon (CFR Title 46) models in terms of durability and ease of use. They are made of quality vinyl protection, tested at 600 volts, 105 degrees Celsius dry and 75 degrees Celsius wet. It can withstand extreme cold (-40 degrees Fahrenheit or Celsius) and protects against ultraviolet radiation, salt water, sulfuric acid, oil, gasoline, warmth, scratched surfaces, and fuel. Type 3 tinned copper stranding, which is of the highest quality and most versatile, provides the best protection against
|
|
|
|
|
AWG or kcmi
|
Carrying wire core(acsr)
|
Phase conductor
|
insulation
|
|
Stell
|
Aluminium
|
|
xlpe
|
|
No.
|
Dia.
|
No.
|
Dia
|
Dia
|
No.
|
Dia
|
Dia
|
|
3*6AWG+1*6AWG
|
1
|
1.68
|
6
|
1.68
|
5.04
|
1
|
4.11
|
4.11
|
1.14
|
3*6AWG+1*6AWG
|
1
|
1.68
|
6
|
1.68
|
5.04
|
7
|
1.55
|
1.55
|
1.14
|
3*4AWG+1*4AWG
|
1
|
2.12
|
6
|
2.12
|
6.36
|
1
|
5.19
|
5.19
|
1.14
|
3*4AWG+1*4AWG
|
1
|
2.12
|
6
|
2.12
|
6.36
|
7
|
1.96
|
5.88
|
1.14
|
3*2AWG+1*2AWG
|
1
|
2.67
|
6
|
2.67
|
8.02
|
7
|
2.47
|
7.42
|
1.14
|
3*1/0AWG+1*1/0AWG
|
1
|
3.37
|
6
|
3.37
|
10.11
|
19
|
1.89
|
9.47
|
1.52
|
3*2/0AWG+1*2/0AWG
|
1
|
3.78
|
6
|
3.78
|
11.35
|
19
|
2.13
|
10.63
|
1.52
|
3*3/0AWG+1*3/0AWG
|
1
|
4.25
|
6
|
4.25
|
12.74
|
19
|
2.39
|
11.94
|
1.52
|
3*4/0AWG+1*4/0AWG
|
1
|
4.77
|
6
|
4.77
|
14.31
|
19
|
2.68
|
13.4
|
1.52
|
3*336.4+1*336.4
|
1
|
3.47
|
18
|
3.47
|
17.36
|
19
|
3.38
|
16.9
|
2.03
|
3*336.4+1*4/0AWG
|
1
|
4.77
|
6
|
4.77
|
14.31
|
19
|
3.38
|
16.9
|
2.03
|
*Applications:
To supply 120 volt aerial service for temporary service at construction sites, outdoor or street lighting. For service at 600 volt
or lower at a conductor temperature of 75℃ maximum.
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
1*6AWG+1*6AWG
|
7
|
1.56
|
563
|
1
|
4.11
|
1.14
|
92
|
85
|
70
|
1*6AWG+1*6AWG
|
7
|
1.56
|
563
|
7
|
1.56
|
1.14
|
94
|
85
|
70
|
1*4AWG+1*4AWG
|
7
|
1.96
|
881
|
1
|
5.19
|
1.14
|
139
|
115
|
90
|
1*4AWG+1*4AWG
|
7
|
1.96
|
881
|
7
|
1.96
|
1.14
|
141
|
115
|
90
|
1*2AWG+1*2AWG
|
7
|
2.47
|
1350
|
7
|
2.47
|
1.14
|
216
|
150
|
120
|
1*1/0AWG+1*1/0AWG
|
7
|
3.12
|
1990
|
19
|
1.89
|
1.52
|
347
|
205
|
160
|
TRIPLEXSERVICEDROP-ALUMINUM CONDUCTOR:
*Applications:
To supply power from the utility's lines to the consumer's weatherhead. For service at 600 volt or less (phase to phase) at a conductor temperature of75℃ maximum for polyethylene insulation or 90℃ maximum for crosslinked insulation.
|
|
|
|
|
|
|
|
|
|
|
|
Dia.mm
|
|
|
2*6AWG+1*6AWG
|
7
|
1.56
|
563
|
1
|
4.11
|
1.14
|
146
|
85
|
70
|
2*6AWG+1*6AWG
|
7
|
1.56
|
563
|
7
|
1.56
|
1.14
|
150
|
85
|
70
|
2*4AWG+1*4AWG
|
7
|
1.96
|
881
|
1
|
5.19
|
1.14
|
219
|
115
|
90
|
2*4AWG+1*4AWG
|
7
|
1.96
|
881
|
7
|
1.96
|
1.14
|
224
|
115
|
90
|
2*2AWG+1*2AWG
|
7
|
2.47
|
1350
|
7
|
2.47
|
1.14
|
338
|
150
|
120
|
2*1/0AWG+1*1/0AWG
|
7
|
3.12
|
1990
|
7
|
3.12
|
1.52
|
544
|
205
|
160
|
2*1/0AWG+1*1/0AWG
|
7
|
3.12
|
1990
|
19
|
1.89
|
1.52
|
545
|
205
|
160
|
2*2/0AWG+l*2/0AWG
|
7
|
3.5
|
2510
|
7
|
3.5
|
1.52
|
671
|
235
|
185
|
2*3/0AWG+l*3/0AWG
|
19
|
2.39
|
3310
|
19
|
2.39
|
1.52
|
830
|
275
|
215
|
2*4/0AWG+l*4/0AWG
|
19
|
3.25
|
4020
|
19
|
3.25
|
1.52
|
1476
|
315
|
245
|
2*336.4+1*336.4
|
19
|
3.38
|
6146
|
19
|
3.38
|
2.03
|
1649
|
420
|
325
|