Medium Voltage power Cable | Cu-Conductor, XLPE insulated, copper tape screened electrical cable

 China Medium Voltage power Cable | Cu-Conductor, XLPE insulated, copper tape screened electrical cable supplier

Medium Voltage power Cable | Cu-Conductor, XLPE insulated, copper tape screened electrical cable image

Get a Quote Email to us

Brand Name :
Chengtiantai Cable

Model Number :
YJV

Certification :
CCC

Place of Origin :
China Mainland

MOQ :
500 m

Price :
On Request

Payment Terms :
L/C, T/T

Delivery Time :
15 working days

Packaging Details :
Steel wooden Drum, On request

Medium Voltage Power Cable single core 6/10 kV, 12/20 kV, 18/30 kV to IEC 60502

XLPE Insulated, Copper conductor, singe core, screened, PVC sheathed

APPLICATIONS

The singe core cables are designed for distribution of electrical power with nominal voltage Uo/U ranging from 6/10 KV to 18/30KV and frequency 50Hz. They are suitable for installation mostly in power supply stations, indoors and in cable ducts, outdoors, underground and in water as well as for installation on cable trays for industries, switchboards and power stations.

CABLE CONSTRUCTION:

1. CONDUCTOR

– Bare copper class 2 to IEC 60228, round, multiwire stranded and compact

2. CONDUCTOR SCREEN

– Inner semi-conducting coating

3. INSULATION

– Core insulation of cross-linked polyethylene (XLPE)

4. INSULATION SCREEN

– Outer conductive layer extruded and per-manently welded with the core insulation

Semi-conducting type
– Over the outer semi-conducting layer, a semiconducting tape must be used.

5. METAL SCREEN

– Annealed copper tapes with a minimum thickness of 0,1 mm.

Separator
– Over the screen as well as under outer sheath, a separating layer must be used (e. g. taping).

6. SHEATH

– Outer sheath of PVC compound

TECHNICAL DATA

>>Temperature range
– during installation up to -5°C

>>Operating temperature
– max. +90°C

>>Short circuit temperature
+250°C (short circuit duration max. 5 s)

>>Minimum bending radius
– 20 x cable Ø

>>Breaking strength: min. 200%
>>Tensile strength: min. 12,5 N/mm2

>>Nominal voltage
– U0/U 6/10 kV, 12/20 kV, 18/30 kV

>>Operating voltage, 50 Hz
– for 6/10 kV = max. 12 kV
– for 12/20 kV = max. 24 kV
– for 18/30 kV = max. 36 kV

>>Test voltage(V/5 min)
– for 6/10 kV = 21 kV
– for 12/20 kV = 42 kV
– for 18/30 kV = 63 kV

6/10 kV XLPE Insulated, Copper conductor, single core, screened, PVC sheathed

No.cores x
cross-sec.
Operation
voltage
max.
Nominal
voltage
U0/U
Insulation
thickness
Sheath
thickness
Nominal
value
Outer Ø
approx.
weight
approx.
Current ratings in air 30℃ Current ratings buried 20℃ maximum DC resistance at 20℃
mm² kV kV mm mm mm kg / km A A Ω/km
1 x 35 rm 12 6/ 10 3.4 1.6 20.6 687 205 190 0.52
1 x 50 rm 12 6/ 10 3.4 1.7 22 855 245 225 0.39
1 x 70 rm 12 6/ 10 3.4 1.7 23.6 1086 305 275 0.27
1 x 95 rm 12 6/ 10 3.4 1.8 25.5 1351 370 330 0.19
1 x 120 rm 12 6/ 10 3.4 1.8 26.9 1622 430 375 0.15
1 x 150 rm 12 6/ 10 3.4 1.9 28.6 1932 490 425 0.12
1 x 185 rm 12 6/ 10 3.4 1.9 30.3 2299 560 480 0.1
1 x 240 rm 12 6/ 10 3.4 2.0 32.7 2864 665 555 0.08
1 x 300 rm 12 6/ 10 3.4 2.1 35.3 3459 765 630 0.06
1 x 400 rm 12 6/ 10 3.4 2.2 38.6 4554 890 725 0.05
1 x 500 rm 12 6/ 10 3.4 2.3 42.2 5574 1030 825 0.04
1 x 630 rm 12 6/ 10 3.4 2.4 45.9 6867 1190 940 0.03

12/20 kV XLPE Insulated, Copper conductor, single core, screened, PVC sheathed

No.cores x
cross-sec.
Operation
voltage
max.
Nominal
voltage
U0/U
Insulation
thickness
Sheath
thickness
Nominal
value
Outer Ø
approx.
weight
approx.
Current ratings in air 30℃ Current ratings buried 20℃ maximum DC resistance at 20℃
mm² kV kV mm mm mm kg / km A A Ω/km
1 x 35 rm 24 12/ 20 5.5 1.8 24.9 860 205 190 0.52
1 x 50 rm 24 12/ 20 5.5 1.8 26.4 1138 245 225 0.39
1 x 70 rm 24 12/ 20 5.5 1.9 28.1 1281 305 275 0.27
1 x 95 rm 24 12/ 20 5.5 1.9 29.9 1570 370 330 0.19
1 x 120 rm 24 12/ 20 5.5 2 31.3 1839 430 375 0.15
1 x 150 rm 24 12/ 20 5.5 2 33.1 2174 490 425 0.12
1 x 185 rm 24 12/ 20 5.5 2.1 34.7 2540 560 480 0.1
1 x 240 rm 24 12/ 20 5.5 2.2 37.1 3120 665 555 0.08
1 x 300 rm 24 12/ 20 5.5 2.2 39.5 3746 765 630 0.06
1 x 400 rm 24 12/ 20 5.5 2.3 44.1 4863 890 725 0.05
1 x 500 rm 24 12/ 20 5.5 2.4 47.6 5905 1030 825 0.04
1 x 630 rm 24 12/ 20 5.5 2.5 51.3 7220 1190 940 0.03

18/30 kV XLPE Insulated, Copper conductor, single core, screened, PVC sheathed

No.cores x
cross-sec.
Operation
voltage
max.
Nominal
voltage
U0/U
Insulation
thickness
Sheath
thickness
Nominal
value
Outer Ø
approx.
weight
approx.
Current ratings in air 30℃ Current ratings buried 20℃ maximum DC resistance at 20℃
mm² kV kV mm mm mm kg / km A A Ω/km
1 x 50 rm 36 18/ 30 8 2 32.6 1363 245 225 0.39
1 x 70 rm 36 18/ 30 8 2 34.3 1614 305 275 0.27
1 x 95 rm 36 18/ 30 8 2.1 36.1 1919 370 330 0.19
1 x 120 rm 36 18/ 30 8 2.1 37.5 2203 430 375 0.15
1 x 150 rm 36 18/ 30 8 2.2 39.3 2556 490 425 0.12
1 x 185 rm 36 18/ 30 8 2.2 40.9 2934 560 480 0.1
1 x 240 rm 36 18/ 30 8 2.3 43.3 3540 665 555 0.08
1 x 300 rm 36 18/ 30 8 2.4 45.7 4191 765 630 0.06
1 x 400 rm 36 18/ 30 8 2.5 49.1 5246 890 725 0.05
1 x 500 rm 36 18/ 30 8 2.6 54.6 6561 1030 825 0.04
1 x 630 rm 36 18/ 30 8 2.7 58.4 7906 1190 940 0.03

*Dimensions and specifications may be changed without prior notice.

MEDIUM VOLTAGE CABLE TESTING

Routine tests: Sample tests: Type tests:
These non-destructive tests are normally carried out on all lengths manufactured.
– Conductor resistivity
– Spark test on oversheath
– Voltage tests on sheath
– D.C. voltage test on oversheath
These potentially destructive tests are normally carried out on every production run.
– Examination of conductor and dimensions
– Hot set test for XLPE insulation
– Insulation and oversheath thickness
– Four hour voltage test
These destructive tests are normally carried out in addition to the above tests on commencement of a particular cable supply to validate its design.
– Electrical type tests including bending and heat cycle
– Non-electrical type tests including mechanical properties after ageing and tests under fire conditions.
Shenzhen chengtiantai cable operates certified management systems compliant with:
Certificat Information
ISO 9001:2008
Quality management systems

Certificat ISO 9001:2008
– Shenzhen chengtiantai cable industry development Co.Ltd. ;
Certified through Guangdong quality Testing CTC Certification Co.Ltd.;

Valid until 9th January 2022
ISO 14001:2004
Environmental management systems

Certificat ISO 14001:2004

– Shenzhen chengtiantai cable industry development Co.Ltd. ;

Certified through Guangdong quality Testing CTC Certification Co.Ltd.;

Valid until 9th January 2022

OHSAS 18001:2007
Assessment specification for occupational health & safety management systemsenvironmental management systems
Certificat OHSAS 18001:2007
– Shenzhen chengtiantai cable industry development Co.Ltd. ;
Certified through Guangdong quality Testing CTC Certification Co.Ltd.;

Valid until 9th January 2022

Some great shot on our manufacturing plant

Located in: Chengtiantai Industrial Park, Guangming New District, Shen zhen P. R. China 518106

WARRANTY

For a period commencing on the date shipped the Goods to Buyer and continuing for a period of 12 months thereafter.

We are China Medium Voltage power Cable | Cu-Conductor, XLPE insulated, copper tape screened electrical cable manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.

Tags: , , ,

FAST AND RELIABLE SERVICE FOR YOUR PROJECT

Contact our trained experts today to find your perfect power solution.

ASK A QUESTION