NA2XBY Cable( 0.6/1 kV AL/XLPE/STA/PVC Power Cable)
0.6/1 kV NA2XBY Cable (AL/XLPE/STA/PVC)
Also Known As:
NA2XBY Low voltage cable, NA2XBY Cable, 0.6/1 kV AL/XLPE/STA/PVC Power Cable
Applications
NA2XBY cable is suitable for AC 50Hz power and distribution lines with rated voltage of 0.6/1kV, which can be used in fixed industrial power applications, underground tunnels, etc. Using steel wire armour offers great mechanical protection, making it rigid with a large radius.
Applicable Standards:
Ge’s 0.6/1 kV NA2XBY Cable (AL/XLPE/STA/PVC) meets or exceeds the following Standards
IEC 60228 Conductors
IEC 60502-1 Power cables with extruded insulation and their accessories for rated voltages from 1kV(Um=1.2kV) up to 35kV(Um=40.5kV) – Part 1: Cables for rated voltages of 1 kV(Um=1.2kV) and 3 kV(Um=3.6kV)
Construction
- Single-core
- Multi core
1. Conductor: Copper or aluminum, Class 1: solid conductor, or Class 2: stranded conductor
2. Insulation: Cross-linked polyethylene XLPE
3. Inner sheath: Polyvinyl chloride PVC
4. Armour: Non-magnetic steel wire
5. Outer sheath: Polyvinyl chloride PVC
1. Conductor: Copper or aluminum, Class 1: solid conductor, or Class 2: stranded conductor
2. Insulation: Cross-linked polyethylene XLPE
3. Filler: Non-hygroscopic material
4. Binder tape: Non-hygroscopic material
5. Inner sheath: Polyvinyl chloride PVC
6. Armour: Low carbon steel wire
7. Outer sheath: Polyvinyl chloride PVC
0.6/1 kV NA2XBY Cable (AL/XLPE/STA/PVC) Specification
Get all the answers to the most frequently asked questions (FAQs) regarding NA2XBY Cable meaning,NA2XBY Cable pdf,NA2XBY Cable full form,NA2XBY Cable current rating,NA2XBY Cable type,NA2XBY Cable manufacturer and much, much more.
0.6/1 kV NA2XBY Cable (AL/XLPE/STA/PVC) manufactured by GE meets or exceeds the requirements of all international standards like ASTM, AS, BS, CSA, DIN, IEC, NFC, SS -etc
Nominal cross sectional area | Insulation thickness | Non-magnetic steel tape thickness | Sheath thickness | Approximate outer diameter | Approx. weight | Max.D.C resistance of conductor(20℃) | Current carrying capacity | |
---|---|---|---|---|---|---|---|---|
mm2 | mm | mm | mm | mm | kg/km | Ω/km | In Air(A) | In Ground(A) |
1X10 | 0.7 | 0.2 | 1.8 | 11.8 | 206 | 3.08 | 58 | 47 |
1X16 | 0.7 | 0.2 | 1.8 | 12.9 | 247 | 1.91 | 75 | 62 |
1X25 | 0.9 | 0.2 | 1.8 | 14.6 | 310 | 1.2 | 100 | 78 |
1X35 | 0.9 | 0.2 | 1.8 | 15.2 | 352 | 0.868 | 120 | 94 |
1X50 | 1.0 | 0.2 | 1.8 | 16.7 | 423 | 0.641 | 145 | 110 |
1X70 | 1.1 | 0.2 | 1.8 | 18.5 | 523 | 0.443 | 190 | 135 |
1X95 | 1.1 | 0.2 | 1.8 | 20.1 | 629 | 0.32 | 235 | 160 |
1X120 | 1.2 | 0.2 | 1.8 | 21.7 | 738 | 0.253 | 270 | 185 |
1X150 | 1.4 | 0.2 | 1.8 | 23.7 | 877 | 0.206 | 310 | 205 |
1X185 | 1.6 | 0.2 | 1.8 | 25.7 | 1031 | 0.164 | 355 | 235 |
1X240 | 1.7 | 0.2 | 1.8 | 28.0 | 1254 | 0.125 | - | - |
1X300 | 1.8 | 0.2 | 1.9 | 31.0 | 1495 | 0.1 | - | - |
1X400 | 2.0 | 0.2 | 2.0 | 35.0 | 1904 | 0.0778 | - | - |
Nominal cross sectional area | Insulation thickness | Non-magnetic steel tape thickness | Sheath thickness | Approximate outer diameter | Approx. weight | Max.D.C resistance of conductor(20℃) | Current carrying capacity | |
---|---|---|---|---|---|---|---|---|
mm2 | mm | mm | mm | mm | kg/km | Ω/km | In Air(A) | In Ground(A) |
2X2.5 | 0.7 | 0.2 | 1.8 | 13.4 | 236 | 12.1 | - | 23 |
2X4 | 0.7 | 0.2 | 1.8 | 14.3 | 269 | 7.41 | - | 30 |
2X6 | 0.7 | 0.2 | 1.8 | 15.3 | 307 | 4.61 | - | 38 |
2X10 | 0.7 | 0.2 | 1.8 | 17.8 | 397 | 3.08 | 50 | 47 |
2X16 | 0.7 | 0.2 | 1.8 | 20.0 | 493 | 1.91 | 64 | 62 |
2X25 | 0.9 | 0.2 | 1.8 | 23.3 | 643 | 1.2 | 86 | 78 |
2X35 | 0.9 | 0.2 | 1.8 | 24.6 | 738 | 0.868 | 105 | 94 |
2X50 | 1.0 | 0.2 | 1.8 | 27.2 | 896 | 0.641 | 125 | 110 |
2X70 | 1.1 | 0.2 | 1.9 | 31.4 | 1164 | 0.443 | 165 | 135 |
2X95 | 1.1 | 0.2 | 2.0 | 35.5 | 1480 | 0.32 | 200 | 160 |
2X120 | 1.2 | 0.5 | 2.2 | 40.2 | 2164 | 0.253 | 235 | 185 |
2X150 | 1.4 | 0.5 | 2.3 | 44.2 | 2572 | 0.206 | 270 | 205 |
2X185 | 1.6 | 0.5 | 2.5 | 48.9 | 3089 | 0.164 | 310 | 235 |
Nominal cross sectional area | Insulation thickness | Non-magnetic steel tape thickness | Sheath thickness | Approximate outer diameter | Approx. weight | Max.D.C resistance of conductor(20℃) | Current carrying capacity | |
---|---|---|---|---|---|---|---|---|
mm2 | mm | mm | mm | mm | kg/km | Ω/km | In Air(A) | In Ground(A) |
3X2.5 | 0.7 | 0.2 | 1.8 | 13.9 | 257 | 12.1 | - | 23 |
3X4 | 0.7 | 0.2 | 1.8 | 14.8 | 296 | 7.41 | - | 30 |
3X6 | 0.7 | 0.2 | 1.8 | 16.0 | 342 | 4.61 | - | 38 |
3X10 | 0.7 | 0.2 | 1.8 | 18.6 | 447 | 3.08 | 50 | 47 |
3X16 | 0.9 | 0.2 | 1.8 | 21.0 | 563 | 1.91 | 64 | 62 |
3X25 | 0.9 | 0.2 | 1.8 | 24.6 | 744 | 1.2 | 86 | 78 |
3X35 | 0.9 | 0.2 | 1.8 | 26.0 | 869 | 0.868 | 105 | 94 |
3X50 | 1.0 | 0.2 | 1.9 | 28.9 | 1074 | 0.641 | 125 | 110 |
3X70 | 1.1 | 0.2 | 2.0 | 33.9 | 1443 | 0.443 | 165 | 135 |
3X95 | 1.1 | 0.5 | 2.2 | 39.0 | 2183 | 0.32 | 200 | 160 |
3X120 | 1.2 | 0.5 | 2.3 | 42.7 | 2593 | 0.253 | 235 | 185 |
3X150 | 1.4 | 0.5 | 2.4 | 47.5 | 3155 | 0.206 | 270 | 205 |
3X185 | 1.6 | 0.5 | 2.6 | 52.1 | 3743 | 0.164 | 310 | 235 |
3X240 | 1.7 | 0.5 | 2.8 | 58.3 | 4641 | 0.125 | 365 | 260 |
3X300 | 1.8 | 0.5 | 2.9 | 63.6 | 5508 | 0.1 | 420 | 290 |
Nominal cross sectional area | Insulation thickness | Non-magnetic steel tape thickness | Sheath thickness | Approximate outer diameter | Approx. weight | Max.D.C resistance of conductor(20℃) | Current carrying capacity | |
---|---|---|---|---|---|---|---|---|
mm2 | mm | mm | mm | mm | kg/km | Ω/km | In Air(A) | In Ground(A) |
4X2.5 | 0.7 | 0.2 | 1.8 | 14.7 | 288 | 12.1 | - | 23 |
4X4 | 0.7 | 0.2 | 1.8 | 15.8 | 334 | 7.41 | - | 30 |
4X6 | 0.7 | 0.2 | 1.8 | 17.0 | 384 | 4.61 | - | 38 |
4X10 | 0.7 | 0.2 | 1.8 | 20.0 | 509 | 3.08 | 50 | 47 |
4X16 | 0.9 | 0.2 | 1.8 | 22.7 | 649 | 1.91 | 64 | 62 |
4X25 | 0.9 | 0.2 | 1.8 | 26.7 | 880 | 1.2 | 86 | 78 |
4X35 | 0.9 | 0.2 | 1.8 | 28.3 | 1040 | 0.868 | 105 | 94 |
4X50 | 1.0 | 0.2 | 2.1 | 32.0 | 1365 | 0.641 | 125 | 110 |
4X70 | 1.1 | 0.5 | 2.1 | 38.5 | 2138 | 0.443 | 165 | 135 |
4X95 | 1.1 | 0.5 | 2.3 | 42.9 | 2638 | 0.32 | 200 | 160 |
4X120 | 1.2 | 0.5 | 2.4 | 47.4 | 3202 | 0.253 | 235 | 185 |
4X150 | 1.4 | 0.5 | 2.6 | 52.3 | 3847 | 0.206 | 270 | 205 |
4X185 | 1.6 | 0.5 | 2.7 | 57.5 | 4585 | 0.164 | 310 | 235 |
4X240 | 1.7 | 0.5 | 3.0 | 64.3 | 5709 | 0.125 | 365 | 260 |
4X300 | 1.8 | 0.5 | 3.1 | 70.3 | 6805 | 0.1 | 420 | 290 |
Nominal cross sectional area | Insulation thickness | Non-magnetic steel tape thickness | Sheath thickness | Approximate outer diameter | Approx. weight | Max.D.C resistance of conductor(20℃) | Current carrying capacity | |
---|---|---|---|---|---|---|---|---|
mm2 | mm | mm | mm | mm | kg/km | Ω/km | In Air(A) | In Ground(A) |
5X2.5 | 0.7 | 0.2 | 1.8 | 15.6 | 321 | 12.1 | - | 23 |
5X4 | 0.7 | 0.2 | 1.8 | 16.8 | 376 | 7.41 | - | 30 |
5X6 | 0.7 | 0.2 | 1.8 | 18.2 | 443 | 4.61 | - | 38 |
5X10 | 0.7 | 0.2 | 1.8 | 21.6 | 592 | 3.08 | 50 | 47 |
5X16 | 0.7 | 0.2 | 1.8 | 24.6 | 763 | 1.91 | 64 | 62 |
5X25 | 0.9 | 0.2 | 1.8 | 29.0 | 1029 | 1.2 | 86 | 78 |
5X35 | 0.9 | 0.2 | 1.9 | 31.0 | 1236 | 0.868 | 105 | 94 |
5X50 | 1.0 | 0.2 | 2.1 | 35.7 | 1616 | 0.641 | 125 | 110 |
5X70 | 1.1 | 0.5 | 2.3 | 42.4 | 2528 | 0.443 | 165 | 135 |
5X95 | 1.1 | 0.5 | 2.4 | 47.2 | 3172 | 0.32 | 200 | 160 |
5X120 | 1.2 | 0.5 | 2.6 | 51.8 | 3801 | 0.253 | 235 | 185 |
5X150 | 1.4 | 0.5 | 2.7 | 57.6 | 4604 | 0.206 | 270 | 205 |
5X185 | 1.6 | 0.5 | 2.9 | 63.8 | 5574 | 0.164 | 310 | 235 |
5X240 | 1.7 | 0.5 | 3.2 | 70.7 | 6859 | 0.125 | 365 | 260 |
5X300 | 1.8 | 0.5 | 3.4 | 78.0 | 8305 | 0.1 | 420 | 290 |
Nominal cross sectional area | Insulation thickness | Non-magnetic steel tape thickness | Sheath thickness | Approximate outer diameter | Approx. weight | Max.D.C resistance of conductor(20℃) | Current carrying capacity | |
---|---|---|---|---|---|---|---|---|
mm2 | mm | mm | mm | mm | kg/km | Ω/km | In Air(A) | In Ground(A) |
3X4+1X2.5 | 0.7/0.7 | 0.2 | 1.8 | 15.5 | 318 | 7.41/12.1 | - | 30 |
3X6+1X4 | 0.7/0.7 | 0.2 | 1.8 | 16.8 | 371 | 4.61/7.41 | - | 38 |
3X10+1X6 | 0.7/0.7 | 0.2 | 1.8 | 19.3 | 478 | 3.08/4.61 | 50 | 47 |
3X16+1X10 | 0.7/0.7 | 0.2 | 1.8 | 22.1 | 615 | 1.91/3.08 | 64 | 62 |
3X25+1X16 | 0.9/0.7 | 0.2 | 1.8 | 25.1 | 794 | 1.2/1.91 | 86 | 78 |
3X35+1X16 | 0.9/0.7 | 0.2 | 1.8 | 26.8 | 926 | 0.868/1.91 | 105 | 94 |
3X50+1X25 | 1/0.9 | 0.2 | 1.9 | 30.2 | 1175 | 0.641/1.2 | 125 | 110 |
3X70+1X35 | 1.1/0.9 | 0.2 | 2.0 | 35.1 | 1570 | 0.443/0.868 | 165 | 135 |
3X95+1X50 | 1.1/1.0 | 0.5 | 2.2 | 40.4 | 2359 | 0.32/0.641 | 200 | 160 |
3X120+1X70 | 1.2/1.1 | 0.5 | 2.3 | 45 | 2886 | 0.253/0.443 | 235 | 185 |
3X150+1X70 | 1.4/1.1 | 0.5 | 2.5 | 49.1 | 3396 | 0.206/0.443 | 270 | 205 |
3X185+1X95 | 1.6/1.1 | 0.5 | 2.8 | 54.3 | 4070 | 0.164/0.32 | 310 | 235 |
3X240+1X120 | 1.7/1.2 | 0.5 | 2.8 | 59.1 | 4855 | 0.125/0.253 | 365 | 260 |
3X300+1X150 | 1.8/1.4 | 0.5 | 3.0 | 66 | 6028 | 0.1/0.206 | 420 | 290 |
Nominal cross sectional area | Insulation thickness | Non-magnetic steel tape thickness | Sheath thickness | Approximate outer diameter | Approx. weight | Max.D.C resistance of conductor(20℃) | Current carrying capacity | |
---|---|---|---|---|---|---|---|---|
mm2 | mm | mm | mm | mm | kg/km | Ω/km | In Air(A) | In Ground(A) |
4X4+1X2.5 | 0.7/0.7 | 0.2 | 1.8 | 16.3 | 365 | 7.41/12.1 | - | 30 |
4X6+1X4 | 0.7/0.7 | 0.2 | 1.8 | 17.7 | 429 | 4.61/7.41 | - | 38 |
4X10+1X6 | 0.7/0.7 | 0.2 | 1.8 | 20.3 | 561 | 3.08/4.61 | 50 | 47 |
4X16+1X10 | 0.7/0.7 | 0.2 | 1.8 | 24 | 728 | 1.91/3.08 | 64 | 62 |
4X25+1X16 | 0.9/0.7 | 0.2 | 1.8 | 28.1 | 974 | 1.2/1.91 | 86 | 78 |
4X35+1X16 | 0.9/0.7 | 0.2 | 1.9 | 29.6 | 1134 | 0.868/1.91 | 105 | 94 |
4X50+1X25 | 1/0.9 | 0.2 | 2.0 | 34 | 1505 | 0.641/1.2 | 125 | 110 |
4X70+1X35 | 1.1/0.9 | 0.5 | 2.2 | 40.3 | 2351 | 0.443/0.868 | 165 | 135 |
4X95+1X50 | 1.1/1.0 | 0.5 | 2.3 | 44.8 | 2907 | 0.32/0.641 | 200 | 160 |
4X120+1X70 | 1.2/1.1 | 0.5 | 2.6 | 50.2 | 3588 | 0.253/0.443 | 235 | 185 |
4X150+1X70 | 1.4/1.1 | 0.5 | 2.8 | 54.6 | 4215 | 0.206/0.443 | 270 | 205 |
4X185+1X95 | 1.6/1.1 | 0.5 | 2.9 | 60.5 | 5133 | 0.164/0.32 | 310 | 235 |
4X240+1X120 | 1.7/1.2 | 0.5 | 3.0 | 67.1 | 6289 | 0.125/0.253 | 365 | 260 |
4X300+1X150 | 1.8/1.4 | 0.5 | 3.2 | 73.7 | 7544 | 0.1/0.206 | 420 | 290 |
Nominal cross sectional area | Insulation thickness | Non-magnetic steel tape thickness | Sheath thickness | Approximate outer diameter | Approx. weight | Max.D.C resistance of conductor(20℃) | Current carrying capacity | |
---|---|---|---|---|---|---|---|---|
mm2 | mm | mm | mm | mm | kg/km | Ω/km | In Air(A) | In Ground(A) |
3X4+2X2.5 | 0.7/0.7 | 0.2 | 1.8 | 16.6 | 354 | 7.41/12.1 | - | 30 |
3X6+2X4 | 0.7/0.7 | 0.2 | 1.8 | 18 | 416 | 4.61/7.41 | - | 38 |
3X10+2X6 | 0.7/0.7 | 0.2 | 1.8 | 20.9 | 531 | 3.08/4.61 | 50 | 47 |
3X16+2X10 | 0.7/0.7 | 0.2 | 1.8 | 24 | 694 | 1.91/3.08 | 64 | 62 |
3X25+2X16 | 0.9/0.7 | 0.2 | 1.8 | 28.1 | 920 | 1.2/1.91 | 86 | 78 |
3X35+2X16 | 0.9/0.7 | 0.2 | 1.9 | 29.6 | 1034 | 0.868/1.91 | 105 | 94 |
3X50+2X25 | 1/0.9 | 0.2 | 2.0 | 34 | 1400 | 0.641/1.2 | 125 | 110 |
3X70+2X35 | 1.1/0.9 | 0.5 | 2.2 | 40.3 | 2153 | 0.443/0.868 | 165 | 135 |
3X95+2X50 | 1.1/1.0 | 0.5 | 2.3 | 44.8 | 2658 | 0.32/0.641 | 200 | 160 |
3X120+2X70 | 1.2/1.1 | 0.5 | 2.5 | 50.2 | 3329 | 0.253/0.443 | 235 | 185 |
3X150+2X70 | 1.4/1.1 | 0.5 | 2.6 | 54.6 | 3790 | 0.206/0.443 | 270 | 205 |
3X185+2X95 | 1.6/1.1 | 0.5 | 2.8 | 60.5 | 4575 | 0.164/0.32 | 310 | 235 |
3X240+2X120 | 1.7/1.2 | 0.5 | 3.0 | 67.1 | 5564 | 0.125/0.253 | 365 | 260 |
3X300+2X150 | 1.8/1.4 | 0.5 | 3.2 | 73.7 | 6801 | 0.1/0.206 | 420 | 290 |