GB1102 24KV Transmission Line Outdoor Vacuum Circuit Breaker

 China GB1102 24KV Transmission Line Outdoor Vacuum Circuit Breaker supplier

GB1102 24KV Transmission Line Outdoor Vacuum Circuit Breaker image

Get a Quote Email to us

Brand Name :
Suntech

Model Number :
ZW32-24

Certification :
ISO

Place of Origin :
Ningbo,China

MOQ :
1 PCS

Price :
Negotiation

Payment Terms :
L/C , T/T

Supply Ability :
60000 pcs per month

Delivery Time :
25-30 days after Payment

Packaging Details :
Exported Wooden Case

Product Name :
Outdoor Vacuum Circuit Breaker

Rated Voltage :
24KV

Rated Frequency :
50/60hz

Poles Number :
3

BCD Curve :
A

Altitude :
≤2000m

Ambient temperature :
-40°C-+40°C

Wind speed :
35m/s

Ambient pllution :
IV

Earthquake intensity :
≤ 8 degre

24kV Transmission Power Line Outdoor Vacuum Circuit Breaker

ZW32-24 type outdoor vacuum circuit breaker is rated voltage 24kV, three-phase AC 50/60Hz outdoor distribution equipment. Mainly used for breaking, closing power system load current, overload current and short circuit Current. For substation and industrial and mining enterprises distribution system protection and control of workplace use, and frequent operation of rural power grids. The circuit breaker vacuum interrupter technique using solid seal, external insulation silicon Rubber sleeve, long life and high relibility, actuator can be miniaturized, highly rliable spring mechanism may also be advanced permanent magnet body. You can also configure isolating switches and itelligent controllers, with But when slicer kind of coincidence Used, enabling four remote functions and distribution automation.

Name Unit Data
Rated voltage KV 24
Rated power frequency Hz 50/60
Rated current KA 630
Rated short-circuit breaking current KA 20
Rated peak withstand current(peak) KA 50
Rated short-time withstand current KA 20
Rated short-circuit making current(peak) KA 50
Mechanical life Secondary 10000
Rated short-circuit breaking current breaking times Secondary 30

Power frequency withstand voltage

(1min) :vacuum fracture,white, on the groundfracture

KV 65/79

Lighting impulse withstand votage

(peak) and white, right fracture

KV 125/145

Secondary circuit 1min power

frequency withstand voltage

KV 2

Standard

1. GB1984 "AC high voltage circuit breakers"

2. GB1102 "nigh-oltage switch and control equipment standards common technical requirements"

3. GB311.1-6 "insulated high voltage transmission and distribution equipment."

4. GB763 "AC high voltage electrical work in long-term fever"

5. GB2706 "AC high voltage electrical dynamic and thermal stability test methods"

6. GB3309 "high voltage switch at room temperature mechanical test"

7. DL / T593 "common ordering technology high voltage switch"

Ambient condition

1. ambient air temperature: + 40°C ~ -40 °C

2. a height of not more than 2000 meters above sea level

3. the wind speed is not greater than 35m/s

4. anti-contamination level for grade IV

5. the earthquake intensity does not exceed 8 degrees

6. no fire, explosion, severe chemical corrosion of the place

We are China GB1102 24KV Transmission Line Outdoor Vacuum Circuit Breaker manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.