GB 1984 50Hz 40.5KV Indoor Vacuum Circuit Breaker

 China GB 1984 50Hz 40.5KV Indoor Vacuum Circuit Breaker supplier

GB 1984 50Hz 40.5KV Indoor Vacuum Circuit Breaker image

Get a Quote Email to us

Brand Name :
Suntech

Model Number :
ZN85-40.5

Certification :
ISO

Place of Origin :
Ningbo,China

MOQ :
1 PCS

Price :
Negotiation

Payment Terms :
L/C , T/T, Western Union, MoneyGram

Supply Ability :
20000 pcs per month

Delivery Time :
30-35 days after Payment

Packaging Details :
Exported Wooden Boxes

Type :
Vacuum Circuit Breaker

Rated Voltage :
40.5KV

Ambient temperature :
-40°C-+40°C

Altitude :
≤1000m

BCD Curve :
A

Rated Frequency :
50/60HZ

High Voltage 40.5KV Indoor Vacuum Circuit Breaker

ZN85 indoor hghvoltage alternating-current vacum crcit breaker has a frequency of 50Hz and a rated vlage of 40.5kv. It aplies to the electrical equipment control and protection in industrial and mining enterprises, power plants and substations, particularly to the places needing frequent operatin. It can be fixed in a switch cabinet or itatled on a handcart.

With stable performance and convenient inalatin, it is the best choice for the control and protecion of high-voltage power trasmission and distribution systems.

Overall dimension of ZN85 -40 5(insulating cylinder handcart) indoor high-voltage alternating-current circuit breaker

1.1 Technical parameters

ltem Unit Reference value
Rated voltage kV 40.5
Rated insulation level Lightning impulse withstand voltage kV 185
1min power-frequency withstand voltage kV 95
Rated frequency Hz 50/60
Rated current A 630/1250/1600/2000/2500/3150
Rated short-circuit breaking current kA 20/25/31.5
Rated short-circuit making current (peak value) kA 50,63,80
Rated short-time withstand current kA 20/25/31.5
Rated withstand current (peak value) kA 50,63,80
Required operation sequence O-0.3s-CO-180s-CO
Rated short-circuit duration s 4
Times of making-breaking with the rated short-circuit current Times 30
Mechanical life M2 level
Weight kg 350

1.2 Mechanical parameters

Item Unit Reference value
Gap of contacts mm 20±2
Contact overtravel mm 6±1
Average making speed m/s 0.6±0.2
Average breaking speed m/s 1.5-2.0
Bounce time in contact making ms ≤3
Non-synchronous making/breaking of contact ms ≤2
Resistance of the circuit of each phase μΩ ≤80
Permissible total wear thickness of the movingfixed contact mm 3

Standard

1. IEC 62271-100 High-voltage aternatingcurrent crcuit-reakers3.6 kV and less than 40.5 kV

2. GB/T 11022-2011 Common specifications for high-voltage switchgear and controlgear standards

3. GB 1984 High-voltage ateratingcrrent crcuitbreakers

4. GB 311.1 Insulation co-ordination for high voltage transmission and distribution equipment

Operating conditions

1. Ambient temperature: – 40℃-+40℃ (below 35℃ within 24 hours)

2. Relative humidity:≤95% (daily average) or≤90% (monthly average)

3. Altitude: ≤1000m

We are China GB 1984 50Hz 40.5KV Indoor Vacuum Circuit Breaker manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.

Tags: , , ,

FAST AND RELIABLE SERVICE FOR YOUR PROJECT

Contact our trained experts today to find your perfect power solution.

ASK A QUESTION