70 Sq mm Concentric XLPE Insulated Power Cable , XLPE Aluminium Cable NA2XCY
70 Sq mm Concentric XLPE Insulated Power Cable , XLPE Aluminium Cable NA2XCY image
Brand Name :
SHANCABLE
Model Number :
YJLV,YXV-U,NA2XY
Certification :
ISO,CE,IEC,TUV,KEMA
Place of Origin :
Shanghai, China
MOQ :
Negotiable
Price :
Negotiable
Payment Terms :
L/C, T/T
Supply Ability :
100KM/Week
Delivery Time :
10 Days
Packaging Details :
Wooden Drum
Rated Voltage :
0.6/1kV
Conductor type :
Stranded Conductor (Class 2)
Core Mark :
Number or Color Strip
Sheath Mark :
ink Printing or Embossing
Insulation :
XLPE rated at 90℃
Standard :
IEC/BS/UL/GB
70 Sq mm Concentric XLPE Insulated Power Cable , XLPE Aluminium Cable NA2XCY
Applications: XLPE Insulated Cable is used as power distribution and transmission line at rated voltage 0.6/1KV.
Construction:
Conductor | Aluminum Conductor as per IEC 60228,Class 2 |
Circular or Shaped conductor | |
Insulation | XLPE (Cross-Linked Polyethylene) rated at 90℃,many color optional |
Metallic Screen optional | Copper tape or copper wires braiding optional |
Sheath | PVC or FR-PVC type ST2 to IEC 60502, black or red or customization |
Ordering Advice
Rated Voltage
Application Standard: IEC/BS/UL/GB
Number of Cores
Conductor Size & Construction
Type of Insulation
Armored or unarmored. If armor, the armor type & material
The Requirement of Sheath
Length of Cable & Packing Requirement
Other Requirement
Technical data: Rated voltage:0.6/1kV Low Voltage
Maximum Conductor Temperature: under normal (90℃), emergency (130℃) or short circuit no more than 5 s (250℃) conditions.
Min. Ambient Temp. 0 OC, after installation and only when cable is in a fixed position
Min. Bending Radius: 20 x cable O.D for single core without armor
15 x cable O.D for multi core without armor
15 x cable O.D for single core with armor
12 x cable O.D for multi core with armor
Standards: International: IEC 60502, IEC 60228, (IEC 60332-3 for FR-type only)
China: GB/T 12706, (GB/T 18380-3 for FR-type only)
Other standards such as BS, DIN, VDE and ICEA upon request
Installation
1. The installation temperature should not over 20℃, If the ambient temperature is lower than 0℃, the cable should be preheated.
2. The bending radius of cable should not less than 8 times.
3. After installation, the cable should with stand voltage test for 15min. 3.5kv D.C.
Technical parameter:
Nom. Cross-section of conductor | Insulation Thickness | Sheath Thickness | Approx. O.D. | Approx. Weight | Max. D.C Resistance of Conductor (20 ℃) | Testing Voltage A.C | Current Rating | |
mm2 | mm | mm | mm | kg/km | Ω /km | kV/5min | In air (A) | In soil(A) |
1×70 | 1.1 | 1.5 | 14 | 336 | 0.443 | 3.5 | 215 | 225 |
3×70 | 1.1 | 2.0 | 30 | 970 | 0.443 | 3.5 | 170 | 175 |
4×70 | 1.1 | 2.0 | 32 | 1192 | 0.443 | 3.5 | 170 | 175 |
3×70+1×35 | 1.1 | 2.0 | 31 | 1085 | 0.443 | 3.5 | 170 | 175 |
Packing and shipping: We are capable of meeting the strictest delivery schedules according to per purchase order. Meeting the deadline is always the top priority as any delay in the delivery of cable can contribute to overall project delay and cost overrun.
Cable is supplied in wooden reels, corrugated boxes and coils. Cable ends are sealed with BOPP self-adhesive tape and non-hygroscopic sealing caps to protect the cable ends from moisture. The required marking shall be printed with a weather-proof material on the outsides of drum according to customer's requirement.
We are China 70 Sq mm Concentric XLPE Insulated Power Cable , XLPE Aluminium Cable NA2XCY manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Tags: xlpe insulated cable, XLPE Insulated Power Cable, xlpe insulation cable