10KV Overhead Insulated Cable JKLYJ Aluminum Core For Power Transmission
10KV Overhead Insulated Cable JKLYJ Aluminum Core For Power Transmission image
10KV Overhead Insulated Cable JKLYJ Aluminum Core For Power Transmission
Application Properties
Rated voltage is up to and including 1KV, 10KV.
The conductor long-term maximum working temperature: PVC and PE insulation should not exceed 70 °C,XLPE insulation should not exceed 90°C.
During short circuit (maximum permanent time is not more than 5 seconds), the maximum temperature of cable conductor : XLPE insulation 250°C, High-density polyethylene insulation 150°C;PVC 160°C
When laying the cable, minimum ambient temperature of laying should not be lower than -20°C.
The minimum bending radius (D is cable out diameter, d is conductor outer diameter):
Rated voltage 1KV and below: cable outer diameter (D) is less than 25mm, bending radius should not be less than 4D, cable diameter (D) is 25mm and above, shall not be less than 6D;
Rated voltage 10KV cable: bending radius of single core cable is 20 (D + d) ± 5% mm, multi-conductor cable, 15 (D + d) ± 5% mm.
10KV XLPE Insulated JKLYJ Aluminum Core Overhead insulated cable
No. of Core abc cable | 1 , 2, 3, 4 , 5 , 3+1 , 3+2 , 4+1 |
Nominal cross section (mm2) | 10mm2 , 16mm2 , 25mm2 , 35mm2 , 50mm2 , 70mm2 , 95mm2 , 120mm2 , 150mm2 , 185mm2 , 240mm2 , 300mm2 and so on. |
Uo/U (kv) | 0.6/1KV |
Insulation | PVC , PE , XLPE |
Conductor | Strand Aluminum Covered Steel wire |
Packing | Steel – wooden drum |
Application | for overhead power transmission |
1.Rated Voltage 1kV
Marks: K is Neutral conductor
2. Rated Voltage 10kV
Marks: K is Neutral conductor, A is steel material, B is aluminum material
10KV XLPE Insulated JKLYJ Aluminum Core Overhead insulated cable
We are China 10KV Overhead Insulated Cable JKLYJ Aluminum Core For Power Transmission manufacture and supplier,You can get more details with Email,you will get cheap price or factory price.
Tags: abc overhead cable, overhead aerial cable, Overhead Insulated Cable